Mounting Devices In Cabinet; Table 2-2 Cabinet Mounting Requirements - Honeywell PE SC1430 Planning, Installation And Service Manual

Table of Contents

Advertisement

2. Platform Installation
2.4. Installing the Server in a Cabinet

Mounting devices in cabinet

Servers can be mounted in a cabinet using the fixed or slide mount options. Due to
safety and center-of-gravity considerations, servers must be mounted starting at the
bottom of the cabinet. The maximum number of computing nodes mountable in a 1-
meter deep cabinet (MP-C1MCB1) is determined by the mix of servers, workstations,
human interface KVM switch/console, whether "fixed" or "slide mount" hardware is
used and total power dissipation. The mounting rail height available in any cabinet is
40U (U is 1.75 inches). Due to AC power and thermal constraints the total number of
computing nodes allowed to be mounted in the 800mm deep cabinet (MP-C8LCB1) must
not exceed nine (9) computing nodes. The various devices mounted in the cabinet
require RETMA standard cabinet openings as specified in Table 2-2. Space required for
other devices not listed below can be found in the corresponding device manuals.

Table 2-2 Cabinet Mounting Requirements

Option
Slide mounted
Fixed mounted
Human interface: 8
port KVM switch; 15-
inch LCD; keyboard &
cursor device
MAU
34
PE SC1430-Based Honeywell Server PE SC1430-Based Honeywell Server
Rack Space
Needed
5U
Any unused space must have a blank
8.75 inches
front panel and air duct baffle installed
22.2 cm
in the unused space to ensure proper
airflow in the cabinet.
4U
Maximum number of computing nodes
7.00 inches
will be determined by total power
17.8 cm
dissipation.
1U
Mount in rack space 16U on telescopic
1.88 inches
slides.
4.78 cm
None
Mounted on the air baffle duct on the
left rear corner of the cabinet (when
viewed from the rear door) near the
vertical cable duct.
Honeywell
Mounting Requirements
Release Independent
12/2007

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents