Cabinet Spacing Requirements - Honeywell HP ProLiant DL360P Gen8 Service Manual

Table of Contents

Advertisement

Chapter 3 - Installation
3.2.1
Grounding consoles and cabinets
The TPN System Installation Manual, SW20-600 , provides information on grounding furniture, including
the following:
Ground Wiring Overview
l
Grounding LCN Cabinets and Stations
l
Cabinet Logic Ground
l
Grounding LCN Cables
l
WARNING
The power supply circuit is connected to AC power. The power control switch on the front panel
only enables the power supply circuit outputs.
ATTENTION
It is strongly recommended that you connect the power cord to a clean power source with backup
such as an Uninterruptible Power Source (UPS).
3.3

Cabinet spacing requirements

Due to thermal constraints, only one HP ProLiant DL360p Gen8 server can be mounted on a new build
1-meter deep Honeywell MP-C1MCB1 cabinet. The server must be mounted on rack space interval
11U through 15U counting from the bottom of the cabinet and moving up. Install a 1U air duct baffle and
blank front panel in the rails directly above the server.
The room ambient temperature must be kept between 10∨dm; and 30∨dm; C (50∨dm; to 86∨dm; F).
3.3.1
Unused cabinet spaces
ATTENTION
To ensure proper computer cooling and airflow through the cabinet, all the unused rack mount
locations must have a blank front panel and an air duct baffle installed.
The blank front panels and air duct baffles are available in four height options. The following table
provides the four height options and the corresponding part and tab numbers.