Error code
(Hexadecimal)
1BB7H
1BB8H
1BB9H
1BBAH
1BBBH
1BBCH
1BBDH
Downloaded from
ManualsNet.com
Error name
Error details and causes
JOG speed limit value error
The setting value of the detailed parameter 2 "[Pr.31]
JOG speed limit value" is outside the setting range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from OFF
to ON: READY signal [X0] is not turned ON.
At start: The system does not start.
JOG speed limit value error
The setting value of the detailed parameter 2 "[Pr.31]
JOG speed limit value" exceeds "[Pr.8] Speed limit
value".
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from OFF
to ON: READY signal [X0] is not turned ON.
At start: The system does not start.
JOG speed limit value error
The setting value of the detailed parameter 2 "[Pr.31]
JOG speed limit value" is smaller than "[Pr.7] Bias
speed at start".
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from OFF
to ON: READY signal [X0] is not turned ON.
At start: The system does not start.
Manual pulse generator
The setting value of the detailed parameter 2 "[Pr.123]
speed limit value error
Manual pulse generator speed limit value" is outside
the setting range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from OFF
to ON: READY signal [X0] is not turned ON.
At start: The system does not operate.
Manual pulse generator
The setting value of the detailed parameter 2 "[Pr.123]
speed limit value error
Manual pulse generator speed limit value" exceeds the
"speed limit value".
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from OFF
to ON: READY signal [X0] is not turned ON.
At start: The system does not operate.
JOG acceleration time
The setting value of the detailed parameter 2 "[Pr.32]
selection setting error
JOG operation acceleration time selection" is outside
the setting range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from OFF
to ON: READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/rapid stop) of the detailed parameter
2 Rapid stop selection (stop group 3). (Note that the
deceleration stop only occurs during the manual pulse
generator operation.)
JOG deceleration time
The setting value of the detailed parameter 2 "[Pr.33]
selection setting error
JOG operation deceleration time selection" is outside
the setting range.
[Operation status at error occurrence]
When the PLC READY signal [Y0] is turned from OFF
to ON: READY signal [X0] is not turned ON.
At start: The system does not start.
During operation: The system stops with the setting
(deceleration stop/rapid stop) of the detailed parameter
2 Rapid stop selection (stop group 3). (Note that the
deceleration stop only occurs during the manual pulse
generator operation.)
search engine
Remedy
When the PLC READY signal [Y0] is not turned
ON after the setting value is corrected, turn the
PLC READY signal [Y0] from OFF to ON.
When the PLC READY signal [Y0] is not turned
ON after the setting value is set to equal to or
less than "[Pr.8] Speed limit value", turn the PLC
READY signal [Y0] from OFF to ON.
When the PLC READY signal [Y0] is not turned
ON after the setting value is set to equal to or
more than "[Pr.7] Bias speed at start", turn the
PLC READY signal [Y0] from OFF to ON.
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
Set a value equal to or less than the speed limit
value.
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
Correct the setting value, turn the PLC READY
signal [Y0] from OFF to ON.
14 TROUBLESHOOTING
14.5 List of Error Codes
14
639