Step 3. Assemble EDGECABG391 to cabinet

1.
Assemble the base panel assembly to the top of the
cabinet using the 8 #6-32 screws provided.
Torque to 10in-lb. (Nm)
2. Pull the wires that were previously connected to the
twist-n-lock receptacles (Step 2, 2) through the two
grommeted holes in the base panel and terminate to
the fuse blocks. The fuse blocks are labeled A and B.
Attach the wires removed from the A receptacle to
the fuse block labeled A. Repeat for the B block. Each
fuse position is labeled L1, L2, or L3. Terminate red
wire to L1, black wire to L2, and blue wire to L3.
Torque to 25in-lb.
Note: Cover is hidden in figure 8 and figure 9 to show the screw locations and wiring clearly. During assembly the
cover does not need to be removed.