Input Power Cable - ABB ACS560 Hardware Manual

0.75 to 160 kw, 1.0 to 215 hp
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

Input power cable

4. Prepare the ends of the cable as illustrated in the figure.
Note: The bare shield will be grounded 360°. Mark the pigtail made from the shield
as a PE conductor with yellow-and-green color
PE
PE
5. Connect the input power cable as follows:
Connect the twisted shield of the cable to the grounding terminal (5a).
Connect the phase conductors of the cable to the L1, L2 and L3 terminals.
Tighten the screws to the torque given below:
Frame size
L1, L2, L3
6. Connect the braking resistor cable as the motor cable. See step 3.
7. Ground the shield 360° (6a).
5a
5b
R0...R1
N·m
lbf·ft
0.5...0.6
0.4
Electrical installation 93
R2
N·m
lbf·ft
1.2...1.5
0.9...1.1

Hide quick links: