Before you adjust the drive operation limits, make sure that the motor and all
driven equipment can operate throughout the set operation limits.
Before you activate the automatic fault reset or automatic restart functions
of the drive control program, make sure that no dangerous situations can
occur. These functions reset the drive automatically and continue operation
after a fault or supply break. If these functions are activated, the installation
must be clearly marked as defined in IEC/EN/UL 61800-5-1, subclause 6.5.3,
for example, "THIS MACHINE STARTS AUTOMATICALLY".
The maximum number of drive power-ups is five in ten minutes. Too frequent
power-ups can damage the charging circuit of the DC capacitors.
If you have connected safety circuits to the drive (for example, Safe torque off
or emergency stop), validate them at start-up. See separate instructions for
the safety circuits.
Beware of hot air exiting from the air outlets.
Do not cover the air inlet or outlet when the drive is running.
Note:
If you select an external source for the start command and it is on, the drive
will start immediately after fault reset unless you configure the drive for pulse
start. See the firmware manual.
If the drive is in remote control mode, you cannot stop or start the drive with
the control panel.
Only authorized persons are allowed to repair a malfunctioning drive.
Safety instructions 17