Brake Resistor Connection Data For Frames R0; Control Connection Data - ABB ACS560 Hardware Manual

0.75 to 160 kw, 1.0 to 215 hp
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

Frame size
R4
R5
R6
R7
R8
1) See the terms in section
external EMC filter to meet the category 2 standards.
Note 1: Radiated emissions are according to C3 with an internal EMC filter.
Note 2: The internal EMC filter must be connected.
Note 3: Radiated and conducted emissions are according to category C3 with an
internal filter and these cable lengths.
Note 4: Categories C1 and C2 meet requirements for connecting equipment to the
public low-voltage networks.
Brake resistor connection data for frames R0...R3
Short-circuit protection
(IEC/EN 61800-5-1, IEC
6439-1)

Control connection data

External power supply
+24 V DC output
(Term. 10)
Maximum motor cable length, 4 kHz
m
150
150
150
150
150
Definitions (page
168). Applicable for frames R4...R8. Frames R0...R2 require
The brake resistor output is conditionally short-circuit proof
by IEC/EN 61800-5-1 and UL 508C. Rated conditional short-cir-
cuit current as defined in IEC 6439-1.
Maximum power:
Frames size R0...R2: (Without external power supply)
Frames size R3...R5: 25 W, 1.04 A at 24 V AC/DC ±10%
Frames size R6...R8 : 36W, 1.50A (24V AC/DC±10%, standard
configuration)
Supplied from an external power supply through option module
CMOD-01 with frames R3...R5. With frames R6...R8 no options
are needed.
Total load capacity of the outputs is 6.0W (250mA/24V) minus
the power taken by the option modules installed on the board.
Technical data 155
ft
492
492
492
492
492