Wiring with external power supply

1
STO
34
OUT1
35
OUT2
36
SGND
37
IN1
38
IN2
1
Drive
2
Safety PLC
K
Safety relay

Activation switch

In the wiring diagrams, the activation switch has the designation [K]. This
represents a component such as a manually operated switch, an emergency stop
push button switch, or the contacts of a safety relay or safety PLC.
In case a manually operated activation switch is used, the switch must be of
a type that can be locked out to the open position.
The contacts of the switch or relay must open/close within 200 ms of each
other.

Cable types and lengths

ABB recommends double-shielded twisted-pair cable.
Maximum cable lengths:
300 m (1000 ft) between activation switch [K] and drive control unit
60 m (200 ft) between external power supply and control unit
Note: A short-circuit in the wiring between the switch and an STO terminal causes
a dangerous fault. Therefore, it is recommended to use a safety relay (including
wiring diagnostics) or a wiring method (shield grounding, channel separation)
which reduces or eliminates the risk caused by the short-circuit.
The Safe torque off function 197
24 V DC
-
+
13
23
31
K
14
24
32
OUT
Y1
Y2
A1
A2
GND