Motor cable

6. Cut an adequate hole into the rubber grommet. Slide the grommet onto the
cable.
7. Prepare the ends of the input power cable and motor cable as illustrated in the
figure. If you use aluminum cables, put grease on the peeled aluminum cable before
connecting it to the drive. Two different motor cable types are shown in the figures
(7a, 7b).
Note: The bare shield is grounded 360°. Mark the pigtail made from the shield as
a PE conductor with yellow-and-green color.
6
7b
8. Slide the cables through the holes of the lead-through plate and attach the
grommets to the holes (the motor cable to the right and the input power cable to
the left).
9. Connect the motor cable as follows:
Ground the shield 360° under the grounding clamps.
Connect the twisted shield of the cable to the grounding terminal (9a).
Connect the phase conductors of the cable to terminals T1/U, T2/V and T3/W.
Tighten the screws to the torque given in the figure (9b).
7a
7b
PE