202 The Safe torque off function

Use

1.
Open the activation switch, or activate the safety functionality that is wired
to the STO connection.
2. The STO inputs on the drive control unit de-energize, and the control unit cuts
off the control voltage from the output IGBTs.
3. The control program generates an indication as defined by parameter 31.22
(see the firmware manual of the drive).
4. The motor coasts to a stop (if running). The drive will not restart while the
activation switch or safety relay contacts are open.
5. Deactivate the STO by closing the activation switch, or resetting the safety
functionality that is wired to the STO connection.
6. Reset any faults before restarting.
WARNING!
The Safe torque off function does not disconnect the voltage of the main
and auxiliary circuits from the drive. Therefore maintenance work on electrical
parts of the drive or the motor can only be carried out after isolating the
drive from the supply and all other voltage sources.
WARNING!
The drive cannot detect or memorize any changes in the STO circuitry when
the drive control unit is not powered. If both STO circuits are closed and a
level-type start signal is active when the power is restored, it is possible that
the drive starts without a fresh start command. Take this into account in
the risk assessment of the system.
This is also valid when the drive is only powered by a BAPO-xx auxiliary power
extension module or a CMOD-xx multifunction extension module.
WARNING!
Permanent magnet or synchronous reluctance [SynRM] motors only:
In case of a multiple IGBT power semiconductor failure, the drive can produce
an alignment torque which maximally rotates the motor shaft by 180/ p
degrees (with permanent magnet motors) or 180/2 p degrees (with
synchronous reluctance [SynRM] motors) regardless of the activation of the
Safe torque off function. p denotes the number of pole pairs.
Notes:
If a running drive is stopped by using the Safe torque off function, the drive
will cut off the motor supply voltage and the motor will coast to a stop. If this

Hide quick links: