230 Optional panel bus adapters and extension modules
No.
Name/Value
15.01
Extension
module type
BREL
15.02
Detected
extension
module
BREL
15.04
RO status
Bit 0 RO4
Bit 1 RO5
Bit 2 RO6
Bit 3 RO7
15.05
RO force
selection
Bit 0 RO4
Bit 1 RO5
Bit 2 RO6
Bit 3 RO7
15.06
RO forced data
Bit 0 RO4
Bit 1 RO5
Bit 2 RO6
Bit 3 RO7
15.07
RO4 source
Not energized
Energized
For the complete parameter list, refer to the drive firmware manual.
15.08
RO4 ON delay
Description
Activates (and specifies the type of) I/O extension
module.
External relay option BREL-01.
I/O extension module detected on the drive.
External relay option BREL-01.
Displays the status of the relay outputs. This
parameter is read-only.
1 = Relay output 4 is ON.
1 = Relay output 5 is ON.
1 = Relay output 6 is ON.
1 = Relay output 7 is ON.
The electrical statuses of the relay/digital outputs
can be overridden for e.g. testing purposes. A bit in
parameter 15.06 RO forced data is provided for each
relay or digital output, and its value is applied
whenever the corresponding bit in this parameter
is 1.
1 = Force relay output 4 to value of bit 0 of
parameter 15.06 RO forced data .
1 = Force relay output 5 to value of bit 0 of
parameter 15.06 RO forced data .
1 = Force relay output 6 to value of bit 0 of
parameter 15.06 RO forced data .
1 = Force relay output 7 to value of bit 0 of
parameter 15.06 RO forced data .
Allows the data value of a forced relay or digital
output to be changed from 0 to 3.
Force the value of this bit to RO4, if so defined in
parameter 15.05 RO force selection .
Force the value of this bit to RO5, if so defined in
parameter 15.05 RO force selection .
Force the value of this bit to RO6, if so defined in
parameter 15.05 RO force selection .
Force the value of this bit to RO7, if so defined in
parameter 15.05 RO force selection .
Selects a drive signal to be connected to relay
output RO4.
Output is not energized.
Output is energized.
Defines the activation delay for relay output RO4.
Def /
FbEq16/32
None
5
None
5
1 = 1
-
-
-
-
1 = 1
-
-
-
-
1 = 1
-
-
-
-
Not
energized
0
1
...
0.0 s