Procedure 4-6 How to Connect –48 VDC Power Source to Equipment Cabinet (Continued)
Connect the other end of wires to -48 VDC output in accordance with manufacturer's instructions
5
and any applicable local regulations.
The MTS DC plug shall be fixed to the DC connector using the plug's screws.
6
Determining Power Connection Wire Size
110 VAC – 240 VAC Input Power Connections
6802800U74-N September 2009
Wire size recommendations contained herein reflect Motorola engineering
requirements
for proper system operation. Local regulations shall be adhered to in any case and
shall supersede any other specifications in this manual, where applicable.
Wire used for DC connection shall not be smaller than 3.3 mm
2
greater than 5.3 mm
VDC wires. However, if the wire is not color-coded, mark these leads with a
colored tracer on each end. Wire used for AC connection shall not be smaller
2
than 1.3 mm
CSA (#16 AWG) or greater than 2.1 mm
Figure 4-23
and
Figure 4-24
There may be small differences in older configurations.
CSA (#10 AWG). Blue is the color recommended for -48
depicts the newer version of the MTS Junction Panel.
Determining Power Connection Wire Size
2
(#12 AWG) or
2
(#14 AWG).
4-25