Error code
D2A0H
Receive buffer full
D2A1H
Send buffer full
Transmission completion wait timer
D2A2H
timeout
D2A3H
Transient data length error
Header information error in
D2A4H
transient transmission
Target station No. error in transient
D2A5H
transmission
Transient data request source No.
D2A6H
error
Header information error in
D2A7H to D2A8H
transient transmission
Target network No. error in
D2A9H
transient transmission
Target station No. error in transient
D2AAH
transmission
Request source network No. error
D2ABH
in transient transmission
Transient data request source No.
D2ACH
error
D2ADH
Transient data length error
Target station No. error in transient
D2AFH
transmission
D2B0H
Transient transmission failed
D300H
Not support function execution error
Error
• Check the network status using the CC-Link IE Field Network diagnostics
of the programming tool.
• When the target station is overloaded and cannot receive transient data,
send the data to the target/relay station after the load on the station is
reduced.
• Reduce the frequency of transient transmission, and retry the operation.
• Check if the switching hub and the cables at the request source are
connected properly.
• Reduce the frequency of transient transmission, and retry the operation.
• Check if the switching hub and the cables at the request source are
connected properly.
• Correct the number of link dedicated instructions that is simultaneously
executed within the range. (Refer to Section 10.2.2 (1) (c).)
Correct the number of data (frame length) at the request source, and retry
the operation.
Correct the header information at the request source, and retry the
operation.
Correct the target station number at the request source, and retry the
operation.
Correct the request source number at the request source, and retry the
operation.
Correct the header information at the request source, and retry the
operation.
Correct the target network number at the request source, and retry the
operation.
Correct the target station number at the request source, and retry the
operation.
Correct the network number of the request source at the request source,
and retry the operation.
Correct the station number of the request source at the request source,
and retry the operation.
Correct the number of data (frame length) at the request source, and retry
the operation.
Transient data transmission addressed to the own station was requested.
Check the network number and target station number, and retry the
operation.
• Check if the switching hub and the cables at the request source are
connected properly.
• Reduce the frequency of transient transmission, and retry the operation.
Not support function is executed in the CC-Link IE Field network
diagnostics.
Check the support functions of the simple motion module.
12 - 18
Chapter 12 TROUBLESHOOTING
Action

Advertisement

Table of Contents
loading