Number
SB0013
Reserved station specification enable request
Reserved station specification enable request
SB005E
accept status
SB005F
Reserved station specification enabled status
SB0180
Reserved station function disable status
(b)
Restoring reserved station setting
1) Specify the station number to restore reserved station setting in Reserved
station function disable setting (SW0011 to SW0017),
2) Turn on Reserved station specification enable request (SB0013).
3) Reserved station specification enable request accept status (SB005E) is
turned on.
4) When cancellation of the reserved station specification is completed,
Reserved station specification enabled status (SB005F) is turned on.
5) Use Reserved station cancel setting status (SW0181 to SW0187) to check
whether the station returned to the reserved station. When the station
specified as Reserved station disable status is not found on the network,
reserved station function disable status (SB0180) is turned off.
6) When the reserved station setting is restored with error, an error code will be
stored in Result of reserved station function enable (SW0057).
7) Turn off Reserved station specification enable request (SB0013).
Description
Number
SW0011 to
Reserved station function disable setting
SW0017
SW0057
Result of reserved station function enable
SW0181 to
Reserved station cancel setting status
SW0187
11 - 24