(8) Dedicated instructions
The following link special relays (SBs) and link special registers (SWs) are used for
dedicated instructions. (Refer to Chapter 10.)
(a)
Number
(b)
Number
REMFR/REMTO instruction (Refer to Section 10.8, Refer to Section 10.9.)
1) Set the following registers before executing the REMFR/REMTO instructions:
• Number of resends (REMFR/REMTO) (SW001A)
• Response wait timer (REMFR/REMTO) (SW001B)
2) When the REMFR/REMTO instruction is executed, the execution status is
stored in Execution status (REMFR/REMTO) (SW0080 to SW009F).
Description
–
Common link dedicated instructions (except the REMFR and REMTO
instructions)
Processing results of link dedicated instructions can be checked using
Send/receive instruction (1) processing result (SW0030) for channel 1 and
Send/receive instruction (2) processing result (SW0031) for channel 2.
Description
–
Number
SW001A
Number of resends (REMFR/REMTO)
SW001B
Response wait timer (REMFR/REMTO)
SW0080 to
Execution status (REMFR/REMTO)
SW009F
Number
SW0030
Send/receive instruction (1) processing result
SW0031
Send/receive instruction (2) processing result
11 - 22
Chapter 11 PROGRAMMING
Description
Description