(9) Canceling/restoring reserved station setting
Number
SB0012
Reserved station function disable request
Reserved station function disable request accept
SB005C
status
Reserved station function disable completion
SB005D
status
SB0180
Reserved station function disable status
Canceling/restoring reserved station setting is executed using the CC-Link IE Field
Network diagnostics as well as link special relays (SBs) and link special registers (SWs).
However, the station No.1 to 16
(Refer to Section 9.6.)
(Note-1): The range from the station No.1 to 4 is valid in the 4-axis module, and the range from the station
No.1 to 8 is valid in the 8-axis module.
(a)
Canceling reserved station setting
1) Specify the station number to cancel reserved station setting in Reserved
station function disable setting (SW0011 to SW0017).
2) Turn on Reserved station function disable request (SB0012).
3) Reserved station function disable request accept status (SB005C) is turned on.
4) When reserved station setting is cancelled, Reserved station function disable
completion status (SB005D) turns on.
5) Reserved station function disable status (SB0180) is turned on and the station
number of the station in reserved station function disable status is stored in
Reserved station cancel setting status (SW0181 to SW0187).
6) When the reserved station setting is cancelled with error, an error code will be
stored in Result of reserved station function disable (SW0056).
7) Turn off Reserved station function disable request (SB0012).
Description
(Note-1)
cannot be specified as a reserved station.
Number
SW0011 to
Reserved station function disable setting
SW0017
SW0056
Result of reserved station function disable
SW0181 to
Reserved station cancel setting status
SW0187
11 - 23
Chapter 11 PROGRAMMING
Description