Mitsubishi Electric MELSEC-Q Series User Manual page 222

Simple motion module
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

Error code
D041H
Incorrect number of stations
D080H to D084H
Network module failure
Transient data transmission
D0A0H
response wait timeout
Transient data transmission
D0A1H
completion wait timeout
Transient data transmission
D0A2H
processing wait timeout
D0A3H
Transient data transmission error
D0A4H to D0A6H
Transient transmission failed
D0A7H
Transient reception failed
Reserved station specification
D0C0H
failed (another process in progress)
Reserved station cancellation failed
D0C1H
(another process in progress)
Data link stop failed (another
D0C2H
process in progress)
Data link start failed (another
D0C3H
process in progress)
Another station number change
D0C6H
failed (another process in progress)
Another station number setting
D0D0H
failed (another process in progress)
Multiple master stations (including
D0E4H
own station)
Error
• Check the network status using the CC-Link IE Field Network diagnostics
of the programming tool.
• If the number of slave stations per network is more than the number of
connectable stations, reduce it to the number of connectable stations or
less.
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• The hardware of the Simple Motion module may be faulty. Please consult
your local Mitsubishi service center or representative.
• If the own station, or target station is disconnected from the network,
identify the cause of the disconnection and take action.
• When the target station is overloaded and cannot receive transient data,
reduce the frequency of transient transmission and retry the operation.
• Check if the cables and the switching hub are connected properly.
• Reduce the frequency of transient transmission, and retry the operation.
• The hardware of the Simple Motion module may be faulty. Please consult
your local Mitsubishi service center or representative.
• Reduce the frequency of transient transmission, and retry the operation.
• Check if the switching hub and the cables at the request source are
connected properly.
• If the own station, or target station is disconnected from the network,
identify the cause of the disconnection and take action.
• Correct the number of the station for which transient data is to be sent,
and retry the operation.
• Check if the cables and the switching hub are connected properly.
• Reduce the frequency of transient transmission, and retry the operation.
• The hardware of the Simple Motion module may be faulty. Please consult
your local Mitsubishi service center or representative.
• Check if the cables and the switching hub are connected properly.
• Reduce the frequency of transient transmission, and retry the operation.
• The hardware of the Simple Motion module may be faulty. Please consult
your local Mitsubishi service center or representative.
Wait for a while, and reserve the station again.
Wait for a while, and cancel the reserved station setting again.
Wait for a while, and instruct the data link stop again.
Wait for a while, and instruct the data link start again.
Wait for a while, and set the station number of another station.
Wait for a while, and set the station number of another station.
• Check the network status using the CC-Link IE Field Network diagnostics
of the programming tool.
• Check if the cables and the switching hub are connected properly.
• After taking the above actions, power off and on all the stations that
detected this error, or reset them.
12 - 12
Chapter 12 TROUBLESHOOTING
Action

Advertisement

Table of Contents
loading