6.5 PUE Configuration Management

The PUE configuration mode can be set to Standard and User-defined on the ECC800
WebUI. You can enable PUE functions and select a PUE configuration mode based on
requirements.
Feature Description
Issue 07 (2020-03-16)
When L1/L2 is enabled, smart cooling products enter the iCooling teamwork control mode.
The temperature and humidity refer to the values at the air intake vents of the IT cabinets.
After L1/L2 linkage is enabled, if the preceding conditions are not met, an L1/L2 linkage alarm is
generated. In this case, the smart cooling product automatically exits the iCooling teamwork mode
and enters the intelligent teamwork mode.
When L1/L2 is enabled, the T/H threshold can only be set on the ECC800 WebUI.
When L1/L2 is disabled, smart cooling products enter the intelligent teamwork control mode
(teamwork controlof smart cooling products).
If the device electrical energy cannot be collected, disable the PUE function for the scenarios where the
PUE calculation condition is not met, such as the wall-mounted CRAC PDB.
Supports user-defined settings of the PUE and power consumption on the ECC800
WebUI.
Synchronizes the PUE and power consumption calculated by the ECC800 from the
WebUI to the app, and displays the data on the app screen.
The ECC800 connects to the NetEco over a northbound port and can upload the
calculated PUE and power consumption data to the NetEco.