Huawei ECC800 User Manual page 51

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Specifications
Table 3-32 AC actuator technical specifications
Item
Power input
Power output
Wireless
communication
RS485 port
AI/DI detection
BLINK button
Indicators
Table 3-33 AC actuator indicators
Indicator
Power
RUN
Issue 07 (2020-03-16)
Specifications
One AC input, 100–240 V AC.
AC OUT1: two AC outputs, 100–240 V AC, maximum total
current: 5 A.
AC OUT2: one AC output, 100–240 V AC, maximum
current: 5 A.
One wireless communication port, complying with
IEEE802.15.4.
One route of dual RS485 ports, not isolated (reserved).
Two AI/DI dry contacts, connecting to two light buttons.
Press the button for less than 1 second to start blinking.
Hold down the button for 1–5 seconds to search for a network
and start networking.
Hold down the button for more than 10 seconds to clear
network parameters.
Color
Name
Green
Power status
indicator
Green
Running
status
indicator
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Steady on
The power input is normal.
Off
There is no power input.
Off
The power is abnormal or the
board program is loading.
Blinking at
The AC actuator successfully
long intervals
registers with the ECC800 and
the software runs properly (the
indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).
Blinking at
The communication is
short intervals
disconnected or the AC
actuator fails to register with
the ECC800 (the indicator
blinks at 4 Hz, on for 0.125s
and then off for 0.125s).
Blinking
The indicator blinks at super
short intervals for 0.5s
3 Device Description
42