Figure 6-5 Querying the total system input electrical energy
Set Device to ECC800, Performance data to Total electrical energy of system IT
load output, and Statistics mode to Hour, set other query criteria such as Start time
and End time as required, and click Query. Record the increment in total electrical
energy of system IT load output of the ECC800. Increment in total electrical energy of
system IT load output = 56.0 kWh – 50.0 kWh = 6.0 kWh
Figure 6-6 Querying the total electrical energy of system IT load output
Calculate the PUE of the smart module. PUE = Increment in total system input electrical
energy/Increment in total electrical energy of system IT load output = 10.0 kWh/6.0
kWh = 1.67