ECC800 Data Center Controller
User Manual
Step 2 Add a SUNRISE-SCU-20K.
1.
2.
Table 5-5 Adding a SUNRISE-SCU-20K
Path
Choose System
Settings >
Device
Management
and click Add
Device. The
parameters for
adding devices
are displayed.
3.
4.
5.
Step 3 On the Running Parameters tab page, set smart cooling product running parameters,
temperature and humidity parameters, and alarm parameters.
Step 4 On the Controls tab page, set the smart cooling product control parameters (such as on/off
control parameters).
----End
Issue 07 (2020-03-16)
The default value of Monitoring address is 1 for the SUNRISE-SCU-20K.
If multiple SUNRISE-SCU-20K devices are connected to a same smart module, ensure that each
monitoring address of a SUNRISE-SCU-20K is unique.
Log in to the ECC800 WebUI as an administrator.
Add a SUNRISE-SCU-20K.
Parameter
Name
Device attribute
Device type
Connect to
Communications
port
Device address
Click Test Connect to check whether the SUNRISE-SCU-20K connects to the ECC800
properly.
If the SUNRISE-SCU-20K connects to the ECC800 properly, click Confirm. The
connected devices are displayed in the Number of connected devices list.
If the SUNRISE-SCU-20K does not connect to the ECC800 properly, check
whether the cable between the SUNRISE-SCU-20K and the ECC800 is connected
properly, whether the SUNRISE-SCU-20K and ECC800 are running properly, and
whether the input parameters are consistent with the SUNRISE-SCU-20K
parameters.
Choose Monitoring > System > ETH Converter Group > ETH Converter n >
Running Parameters and set Device name to ETH Converter n_Device name.
Choose Monitoring > Air Conditioner > SUNRISE-SCU-20K n > Running
Parameters and set Device name to SUNRISE-SCU-20K_Device name.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select Air Conditioner from the drop-down list
box.
Select SUNRISE-SCU-20K from the drop-down
list box.
Select ETH Converter n from the drop-down list
box.
Select COM1/COM2 from the drop-down list box.
In this example, Device address is set to 2. During
actual configuration, set the device address based
on the actual situation.
5 Power-On Commissioning
91