ECC800 Data Center Controller
User Manual
Step 5 Choose Home > Multi-Module Monitoring. The information about the cascaded ECC800s
is displayed.
Figure 6-2 ECC800 cascading page
Step 6 (Optional) Click the alarm bubble in the Active alarms area in a smart module to view the
corresponding active alarm information.
Step 7 (Optional) Click the pencil icon near Smart Module in a smart module. Then, you can
change the smart module name in the Edit Smart Module Title dialog box.
Step 8 (Optional) Click Link in a smart module on the cascading page to access the corresponding
ECC800 login page.
----End
6.4 (Optional) iCooling Function
Working Principles
The iCooling function includes L1/L2 linkage and linkage between smart cooling product
indoor and outdoor units. Currently, only L1/L2 linkage is supported. The smart cooling
products that support this function are Netcol5000-A025 and Netcol5000-A042.The function
of L1/L2 linkage is to enable smart cooling products to quickly respond to load changes and
implement on-demand cooling. The smart cooling products can be regulated to achieve
optimal energy efficiency.
Issue 07 (2020-03-16)
L1/L2 disabled
For the cold aisle containment in the smart module, all IT cabinets use the cooling
−
capacity in the cold aisle and the temperatures inside the cold aisle are unevenly
distributed due to the uneven air flow.
Copyright © Huawei Technologies Co., Ltd.
6 Feature Description
163