5.7 Commissioning the Cameras and VCN500 (Smart ETH
Gateway Networking Scenario)
A maximum of three cameras can be connected in the smart ETH gateway networking
scenario.
Issue 07 (2020-03-16)
Press the networking switch on the CIM for 2 seconds. The ALM indicator blinks red
once, and the RF_Z indicator turns from steady green to blinking green at super short
intervals, which indicates that the CIM is being networked.
Blinking at long intervals: The indicator is on for 1 second and then off for 1 second alternately.
Blinking at super short intervals: The indicator is on for 0.05 seconds and then off for 0.05 seconds
alternately.
Press the BIM networking switch for 2 seconds. When the RUN/ALM indicator turns
from steady red to blinking green at super short intervals, and finally to blinking green at
long intervals, the BIM connects to the CIM network.
It is recommended that BIMs be networked from the positive battery string terminal according to the
battery cable connection sequence.
Batteries are numbered depending on the sequence of connecting BIMs to the CIMs.
Perform networking operations on the next BIM only after networking for the previous
BIM is successful. Repeat
Press the CIM networking switch for 2 seconds. When the RF_Z indicator on the CIM
turns from blinking green at super short intervals to blinking green at long intervals, the
networking is complete.
After the networking is complete, if the ALM indicator on the CIM is steady on, the number of devices
online is smaller than the value of BIM Number. Check that BIM Number is set to a correct value and
that the BIM is successfully networked.
(Optional) If multiple CIMs are cascaded, repeat
networking for remaining CIMs and BIMs.
Copyright © Huawei Technologies Co., Ltd.
Step 4.2
to add other BIMs to the CIM network.
5 Power-On Commissioning
Step 4.1
to
Step 4.4
to perform
133