8
Connectors
The front of the module has the following connectors:
CHANNEL 1
CHANNEL2
SYNCHRO
(ground)
LEDs
There are two pairs of LEDs at the top of the module. The upper pair is for channel 1 and the lower
pair is for channel 2.
CD1/CD2
TEN1/TEN2
FIP Remote I/O Scanner Documentation:
8-14
Series 90-30 PLC Installation and Hardware Manual – August 2002
9-pin male D connectors for two FIP bus cables. A bus can be disconnected
from the module without disturbing the continuity of the bus. The second bus is
a backup for the first bus; its use is optional.
Connector for a FIP synchronization cable. It requires a mating connector such
as Molex #39-01-4031. The synchronization capability is not used in a Series
90-70 PLC application.
The lug below the Synchro connector is used for the module ground wire
(provided). The other end of the ground wire must be connected to the mounting
bolt on the lower left corner of the baseplate and to chassis ground.
The green Carrier Detected LEDs indicate the presence of a carrier-detect signal
on their respective channels.
The red Transmission Enabled LEDs indicate the module is generating
transmissions on their respective channels.
GFK-1037, Series 90-30 FIP Remote I/O Scanner User's Manual
GFK-1038, FIP Bus Controller User's Manual