Example 2 - ABB Relion 670 Series Applications Manual

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UEN Rev. K
I
s
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
IEC05000753 V2 EN-US
Figure 7:
Figure
7
direction shall be done according to the figure. To protect the line, direction of the directional
functions of the line protection shall be set to
looking towards the line.
4.2.2.2

Example 2

Two IEDs used for protection of two objects and sharing a CT.
Bay control REC670
Application manual
Transformer
I
p
Transformer
protection
IED
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Example how to set CTStarPoint parameters in the IED
shows the normal case where the objects have their own CTs. The settings for CT
© Copyright 2017 Hitachi Power Grids. All rights reserved
I
I
p
p
I
s
Setting of current input:
Set parameter
CTStarPoint with
reference object.
Correct setting is
"ToObject"
"FromObject"
Forward . This means that the protection is
Line
Line
Reverse
Forward
Definition of direction
for directional functions
Line protection
IED
Line as
IEC05000753=IEC05
000753=1=en=Origin
al[1].vsd
Section 4
Analog inputs
SEMOD55055-29 v7
61