ABB Relion 670 Series Applications Manual page 333

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UEN Rev. K
ManEnergDBDL
If the parameter is set to
voltage are below
DLLB , DBLL or Both .
UHighBusEnerg and UHighLineEnerg
The voltage level settings must be chosen in relation to the bus or line network voltage. The
threshold voltages
which the network is considered to be energized. A typical value can be 80% of the base
voltages.
ULowBusEnerg and ULowLineEnerg
The threshold voltages
than the value where the network is considered not to be energized. A typical value can be 40%
of the base voltages.
Because the setting ranges of the threshold voltages
ULowBusEnerg / ULowLineEnerg partly overlap each other, the setting conditions may be such
that the setting of the non-energized threshold value is higher than that of the energized
threshold value. The parameters must therefore be set carefully to avoid overlapping.
UMaxEnerg
This setting is used to block the closing when the voltage on the live side is above the set value
UMaxEnerg .
of
tAutoEnerg and tManEnerg
The purpose of the timer delay settings,
side remains de-energized and that the condition is not due to a temporary interference.
Should the conditions not persist for the specified time, the delay timer is reset and the
procedure is restarted when the conditions are fulfilled again. Circuit breaker closing is thus
not permitted until the energizing condition has remained constant throughout the set delay
setting time.
15.2
Autorecloser for 1 phase, 2 phase and/or 3 phase
operation SMBRREC
15.2.1
Identification
Function Description
Autorecloser for 1 phase, 2 phase and/or 3
phase
Bay control REC670
Application manual
On , manual closing is also enabled when both line voltage and bus
ULowLineEnerg and ULowBusEnerg respectively, and ManEnerg is set to
UHighBusEnerg and UHighLineEnerg have to be set lower than the value at
ULowBusEnerg and ULowLineEnerg , have to be set to a value greater
A disconnected line can have a considerable potential due to, for instance,
induction from a line running in parallel, or by being fed via the extinguishing
capacitors in the circuit breakers. This voltage can be as high as 30% or more
of the base line voltage.
© Copyright 2017 Hitachi Power Grids. All rights reserved
UHighBusEnerg / UHighLineEnerg and
tAutoEnerg and tManEnerg , is to ensure that the dead
IEC 61850
IEC 60617
identification
identification
SMBRREC
5(0 -->1)
IEC15000204 V1 EN-US
Section 15
Control
IP14559-1 v6
M14890-1 v7
ANSI/IEEE C37.2
device number
79
327