ABB Relion 670 Series Applications Manual page 437

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UEN Rev. K
15.9.1
Identification
Function description
Single point generic control 8 signals
15.9.2
Application
The Single point generic control 8 signals (SPC8GAPC) function block is a collection of 8 single
point commands that can be used for direct commands for example reset of LED's or putting
IED in "ChangeLock" state from remote. In this way, simple commands can be sent directly to
the IED outputs, without confirmation. Confirmation (status) of the result of the commands is
supposed to be achieved by other means, such as binary inputs and SPGAPC function blocks.
15.9.3
Setting guidelines
The parameters for the single point generic control 8 signals (SPC8GAPC) function are set via
the local HMI or PCM600.
Operation : turning the function operation On / Off .
There are two settings for every command output (totally 8):
PulseModex : decides if the command signal for output x is Latched (steady) or Pulsed .
tPulsex : if PulseModex is set to Pulsed , then tPulsex will set the length of the pulse (in
seconds).
15.10
AutomationBits, command function for DNP3.0
AUTOBITS
15.10.1
Identification
Function description
AutomationBits, command function
15.10.2
Application
Automation bits, command function for DNP3 (AUTOBITS) is used within PCM600 in order to
get into the configuration the commands coming through the DNP3.0 protocol.The AUTOBITS
function plays the same role as functions GOOSEBINRCV (for IEC 61850) and MULTICMDRCV
(for LON).AUTOBITS function block have 32 individual outputs which each can be mapped as a
Binary Output point in DNP3. The output is operated by a "Object 12" in DNP3. This object
contains parameters for control-code, count, on-time and off-time. To operate an AUTOBITS
Bay control REC670
Application manual
IEC 61850
identification
SPC8GAPC
PSTO is the universal operator place selector for all control functions. Even if
PSTO can be configured to allow LOCAL or ALL operator positions, the only
functional position usable with the SPC8GAPC function block is REMOTE.
IEC 61850
identification
for DNP3
© Copyright 2017 Hitachi Power Grids. All rights reserved
IEC 60617
identification
-
IEC 60617
identification
AUTOBITS
-
Section 15
SEMOD176456-2 v3
ANSI/IEEE C37.2
device number
-
SEMOD176511-4 v7
SEMOD176518-4 v7
SEMOD158589-1 v3
GUID-C3BB63F5-F0E7-4B00-AF0F-917ECF87B016 v4
ANSI/IEEE C37.2
device number
-
SEMOD158637-5 v4
Control
431

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rec670

Table of Contents