Section 8
Current protection
IAmpComp5, IAmpComp30, IAmpComp100
UAmpComp5, UAmpComp30, UAmpComp100
IAngComp5, IAngComp30, IAngComp100
The angle compensation is given as difference between current and voltage angle errors.
The values are given for operating points 5, 30 and 100% of rated current/voltage. The values
should be available from instrument transformer test protocols.
8.13
Directional overpower protection GOPPDOP
8.13.1
Identification
Function description
Directional overpower protection
8.13.2
Application
The task of a generator in a power plant is to convert mechanical energy available as a torque
on a rotating shaft to electric energy.
Sometimes, the mechanical power from a prime mover may decrease so much that it does not
cover bearing losses and ventilation losses. Then, the synchronous generator becomes a
synchronous motor and starts to take electric power from the rest of the power system. This
operating state, where individual synchronous machines operate as motors, implies no risk for
the machine itself. If the generator under consideration is very large and if it consumes lots of
electric power, it may be desirable to disconnect it to ease the task for the rest of the power
system.
Often, the motoring condition may imply that the turbine is in a very dangerous state. The task
of the reverse power protection is to protect the turbine and not to protect the generator
itself.
Steam turbines easily become overheated if the steam flow becomes too low or if the steam
ceases to flow through the turbine. Therefore, turbo-generators should have reverse power
protection. There are several contingencies that may cause reverse power: break of a main
steam pipe, damage to one or more blades in the steam turbine or inadvertent closing of the
main stop valves. In the last case, it is highly desirable to have a reliable reverse power
protection. It may prevent damage to an otherwise undamaged plant.
During the routine shutdown of many thermal power units, the reverse power protection gives
the tripping impulse to the generator breaker (the unit breaker). By doing so, one prevents the
disconnection of the unit before the mechanical power has become zero. Earlier disconnection
would cause an acceleration of the turbine generator at all routine shutdowns. This should
have caused overspeed and high centrifugal stresses.
When the steam ceases to flow through a turbine, the cooling of the turbine blades will
disappear. Now, it is not possible to remove all heat generated by the windage losses. Instead,
the heat will increase the temperature in the steam turbine and especially of the blades. When
192
IEC 61850
identification
GOPPDOP
© Copyright 2017 Hitachi Power Grids. All rights reserved
IEC 60617
ANSI/IEEE C37.2
identification
device number
32
P >
2
DOCUMENT172362-IMG158942
V2 EN-US
1MRK 511 401-UEN Rev. K
SEMOD172360-1 v4
SEMOD176574-2 v4
SEMOD172358-4 v2
Bay control REC670