1MRK 511 401-UEN Rev. K
SuppressMidPos when On suppresses the mid-position during the time tIntermediate of the
connected switches.
The parameter
operate, Sel & Op phase, or only at operate, Op phase.
15.3.9.3
Switch (SXCBR/SXSWI)
tStartMove is the supervision time for the apparatus to start moving after a command
execution is done from the SCSWI function. When the time has expired, the command
supervision is reset, and a cause-code is given.
During the
state. When the time has expired, the command supervision is reset, and a cause-code is given.
The indication of the mid-position at SCSWI is suppressed during this time period when the
position changes from open to close or vice-versa if the parameter
On in the SCSWI function.
If the parameter
new correct end position is reached. If the parameter is set to
output pulse remains active until the timer
tOpenPulse is the output pulse length for an open command. If AdaptivePulse is set to
Adaptive , it is the maximum length of the output pulse for an open command. The default
length is set to 200 ms for a circuit breaker (SXCBR) and 500 ms for a disconnector (SXSWI).
tClosePulse is the output pulse length for a close command. If AdaptivePulse is set to
Adaptive , it is the maximum length of the output pulse for an open command. The default
length is set to 200 ms for a circuit breaker (SXCBR) and 500 ms for a disconnector (SXSWI).
15.3.9.4
Proxy for signals from switching device via GOOSE XLNPROXY
SwitchType setting controls the evaluation of the operating capability. If SwitchType is set
The
Circuit Breaker , the input OPCAP is interpreted as a breaker operating capability, otherwise
to
it is interpreted as a switch operating capability.
Table 58: Operating capability values for breaker/switches
Value
1
2
3
4
5
6
7
tStartMove is the supervision time for the apparatus to start moving after a command
execution is done from the SCSWI function. When the time has expired, the command
supervision is reset, and a cause-code is given.
During the
state. When the time has expired, the command supervision is reset, and a cause-code is given.
The indication of the mid-position at SCSWI is suppressed during this time period when the
position changes from open to close or vice-versa if the parameter
On in the SCSWI function.
Bay control REC670
Application manual
InterlockCheck decides if interlock check should be done at both select and
tIntermediate time, the position indication is allowed to be in an intermediate (00)
AdaptivePulse is set to Adaptive the command output pulse resets when a
Breaker operating capability, CbOpCap
None
Open
Close – Open
Open – Close – Open
Close – Open – Close – Open
Open – Close – Open – Close – Open
more
tIntermediate time, the position indication is allowed to be in an intermediate (00)
© Copyright 2017 Hitachi Power Grids. All rights reserved
Not adaptive the command
tOpenPulsetClosePulse has elapsed.
Switch operating capability, SwOpCap
None
Open
Close
Close and Open
Larger values handled as 4, both Close and Open
Section 15
Control
M16675-3 v8
SuppressMidPos is set to
GUID-7C253FE7-6E02-4F94-96C7-81C9129D925D v1
SuppressMidPos is set to
361