Section 20
Ethernet-based communication
Redundancy : redundant communication is activated when the parameter is set to PRP-0 , PRP-1
or
HSR . The settings for the next access point will be hidden and PhyPortB will show the
second port information. Redundant communication is activated after a common write to IED
is done.
PRP-1 should be used primarily, PRP-0 is intended only for use in existing PRP-networks. PRP-1
and HSR can be combined in a mixed network.
If the access point is not taken into operation, the write option in Ethernet Configuration Tool
can be used to activate the access point.
IEC16000039 V1 EN-US
Figure 259: ECT screen with Redundancy set to PRP-1 on Access point 1 and HSR Access
20.3
Merging unit
20.3.1
Application
The IEC/UCA 61850-9-2LE process bus communication protocol enables an IED to
communicate with devices providing measured values in digital format, commonly known as
Merging Units (MU). The rear access points are used for the communication.
The merging units (MU) are called so because they can gather analog values from one or more
measuring transformers, sample the data and send the data over process bus to other clients
(or subscribers) in the system. Some merging units are able to get data from classical
measuring transformers, others from non-conventional measuring transducers and yet others
can pick up data from both types.
540
point 3
© Copyright 2017 Hitachi Power Grids. All rights reserved
IEC16000039-1-en.vsdx
1MRK 511 401-UEN Rev. K
GUID-E630C16F-EDB8-40AE-A8A2-94189982D15F v1
Bay control REC670
Application manual