ABB Relion 670 Series Applications Manual page 603

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UEN Rev. K
IEEE 1588 (PTP)
Precision Time Protocol (PTP) is enabled/disabled using the Ethernet configuration tool /ECT)
in PCM600.
PTP can be set to On , Off or Slave only . When set to Slave only the IED is connected to the PTP-
group and will synchronize to the grandmaster but cannot function as the grandmaster.
A PTP-group is set up by connecting the IEDs to a network and enabling PTP. To set one IED as
the grandmaster change Priority2 to 127 instead of the default 128.
IEC16000089 V1 EN-US
Figure 285: Enabling PTP in ECT
PTP VLAN tag must have the same value in station clock and in the IED. The default value is
The
set to 0.
PTP VLAN tag does not need to be the same on all access points in one IED. It is possible
The
to mix as long as they are the same for all devices on each subnet.
Setting example
Station bus
Process bus
IEC16000167 V1 EN-US
Figure 286: Example system
Figure
286
the SAM600, and gets its synch from the GPS. Moreover, the REL and REC both acts as a
boundary clock to provide synch to the SAM600. The REL contains a GTM card, which has a PPS
Bay control REC670
Application manual
All protection functions will be blocked if the AppSynch parameter is set to
Synch while there is no 9-2 synchronization source. For more information
please refer to the "IEC/UCA 61850-9-2LE communication protocol" section.
GPS
PTP
PTP
PTP
REC
REL
GTM
PTP
9-2
9-2
PTP
9-2
9-2
9-2
SAM600-TS
SAM600-CT
SAM600-VT
IEC16000167-1-en.vsdx
describes an example system. The REC and REL are both using the 9-2 stream from
© Copyright 2017 Hitachi Power Grids. All rights reserved
PPS
MU
Section 24
Basic IED functions
GUID-424227EC-74A1-4628-8948-C1876840ABFE v3
IEC16000089-1-en.vsdx
597

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rec670

Table of Contents