This protection function is applied to capacitor banks that have CT's to measure the unbalance
current between equal impedance strings of the capacitor bank. The connection types of SCB
are considered with reference to the
the shunt capacitor banks .
For an ungrounded double WYE connection, neutrals of the two WYE sections are tied
together and a normal CT is placed to measure the unbalance current. For a grounded double
WYE connection, neutrals of the two WYE sections are grounded independently, so that a
differential CT is placed to measure the difference of unbalance currents flowing through the
two neutrals.
L1
L2
L3
IEC19000196 V1 EN-US
Figure 109: Grounded/ungrounded double WYE connected SCB with CT arrangement
In the above configurations, the unbalance current is proportional to the positive sequence
current. Hence, the positive sequence component of current is considered as the reference to
measure the unbalance current.
For a grounded/ungrounded single WYE connection, each phase is divided into two main
strings. A differential CT is placed to measure the difference between the unbalance currents
through two strings.
Bay control REC670
Application manual
IEEE standard C37.99-2000 guide for the protection of
I
L1
I
L2
I
L3
C
C
C
C
C
C
C
C
C
C
C
C
N1
I
I
UNB1
N1
Differential CT
I
UNB1
Normal CT
© Copyright 2017 Hitachi Power Grids. All rights reserved
C
C
C
C
C
C
C
C
C
C
C
C
N2
I
N2
IEC19000196-1-en-us.vsdx
Section 10
Unbalance protection
Grounded
Ungrounded
233