Section 15
Control
ACTIVE
Indicates that the auto recloser is active, from start until end of reclaim time.
BLOCKED
Indicates that auto recloser is temporarily or permanently blocked.
CLOSECB
Connect to a binary output for circuit breaker closing command.
COUNT1P, COUNT2P, COUNT3P1, COUNT3P2, COUNT3P3, COUNT3P4 and
COUNT3P5
Indicates the number of auto reclosing shots made for respective shot.
COUNTAR
Indicates the total number of auto reclosing shots made.
INHIBOUT
If the
INHIBIT input is activated it is reported on the INHIBOUT output.
INPROGR
Indicates that an auto recloser sequence is in progress, from start until circuit breaker close
command.
MODE
When a valid integer is connected to the
invalid and the
integer on the
corresponding
PERMIT1P
Permit single-phase trip is the inverse of
for connection to external protection or trip relays. In case of a total loss of auxiliary power,
the output relay drops and does not allow single-phase trip.
PREP3P
Prepare three-phase trip is usually connected to the trip block to force a coming trip to be a
three-phase one. If the auto recloser cannot make a single-phase or two-phase auto reclosing,
the tripping should be three-phase.
READY
Indicates that the auto recloser is ready for a new and complete auto reclosing sequence. It
can be connected to the zone extension if a line protection should have extended zone reach
before auto reclosing.
SETON
Indicates that auto recloser is switched on and operative.
SUCCL
If the circuit breaker closing command is given and the circuit breaker is closed within the set
time interval
340
MODEINT input value will be used instead. The selected mode is reported as an
MODE output. The six possible modes are described in Table
MODEINT integer value.
tUnsucCl , the SUCCL output is activated after the set time interval tSuccessful .
© Copyright 2017 Hitachi Power Grids. All rights reserved
MODEINT input, the selected ARMode setting will be
PREP3P . It can be connected to a binary output relay
1MRK 511 401-UEN Rev. K
54
with their
Bay control REC670
Application manual