Section 12
Multipurpose protection
By defining parameter x equal to the per unit value for the desired pickup for the overload IED
in accordance with the following formula:
x = 116% = 1.16 pu
EQUATION1377 V2 EN-US
formula 3.5can be re-written in the following way without changing the value for the operate
time of the generator stator overload IED:
=
t
op
æ
ç
è
EQUATION1378 V1 EN-US
In order to achieve such protection functionality with one CVGAPC functions the following
must be done:
1.
Connect three-phase generator currents to one CVGAPC instance (for example, GF01)
2.
Set parameter
3.
Set base current value to the rated generator current in primary amperes
4.
Enable one overcurrent step (for example OC1)
5.
Select parameter
= ×
t
k
op
EQUATION1375 V1 EN-US
where:
t
op
k
M
A, B, C and P are user settable coefficients which determine the curve used for Inverse Time Overcurrent
When the equation
the OC1 step in it is obvious that if the following rules are followed:
1.
set k equal to the IEC or ANSI standard generator capability value
2.
set parameter
3.
set parameter
4.
set parameters
5.
set
then the OC1 step of the CVGAPC function can be used for generator negative sequence
inverse overcurrent protection.
1.
select positive sequence current as measuring quantity for this CVGAPC function
2.
make sure that the base current value for CVGAPC function is equal to the generator rated
current
3.
set k = 37.5 for the IEC standard or k = 41.4 for the ANSI standard
4.
set
292
1
×
k
2
x
2
ö
I
1
-
m
÷
×
2
x I
x
ø
r
CurrentInput to value PosSeq
CurveType_OC1 to value Programmable
æ
ö
A
+
B
ç
÷
-
P
è
M
C
ø
is the operating time in seconds of the Inverse Time Overcurrent TOC/IDMT algorithm
is time multiplier (parameter setting)
is ratio between measured current magnitude and set pickup current level
TOC/IDMT calculation
171
is compared with the equation
A_OC1 equal to the value 1/x2
C_OC1 equal to the value 1/x2
B_OC1 = 0.0 and P_OC1 =2.0
StartCurr_OC1 equal to the value x
A_OC1 = 1/1.162 = 0.7432
© Copyright 2017 Hitachi Power Grids. All rights reserved
1MRK 511 401-UEN Rev. K
172
for the inverse time characteristic of
(Equation 170)
(Equation 171)
(Equation 172)
Bay control REC670
Application manual