Section 15
Control
DB_BUS_A
IEC04000518 V1 EN-US
Figure 201: Switchyard layout double circuit breaker
For a double circuit-breaker bay, the modules DB_BUS_A, DB_LINE and DB_BUS_B must be
used.
15.4.8.2
Configuration setting
For application without QB9 and QC9, just set the appropriate inputs to open state and
disregard the outputs. In the functional block diagram, 0 and 1 are designated 0=FALSE and
1=TRUE:
QB9_OP = 1
QB9_CL = 0
QC9_OP = 1
QC9_CL = 0
If, in this case, line voltage supervision is added, then rather than setting QB9 to open state,
specify the state of the voltage supervision:
QB9_OP = VOLT_OFF
QB9_CL = VOLT_ON
If there is no voltage supervision, then set the corresponding inputs as follows:
VOLT_OFF = 1
VOLT_ON = 0
15.4.9
Interlocking for 1 1/2 CB BH
390
QB1
QC1
QA1
QC2
QB61
QB9
QC9
© Copyright 2017 Hitachi Power Grids. All rights reserved
WA1 (A)
WA2 (B)
QB2
QC4
QA2
DB_BUS_B
QC5
QB62
QC3
DB_LINE
en04000518.vsd
1MRK 511 401-UEN Rev. K
M13584-4 v4
M13584-6 v5
IP14173-1 v3
Bay control REC670
Application manual