1MRK 511 401-UEN Rev. K
Remember that values of parameters set elsewhere are linked to the information on a report.
Such parameters are, for example, station and object identifiers, CT and VT ratios.
18.7
Logical signal status report BINSTATREP
18.7.1
Identification
Function description
Logical signal status report
18.7.2
Application
The Logical signal status report (BINSTATREP) function makes it possible to poll signals from
various other function blocks.
BINSTATREP has 16 inputs and 16 outputs. The output status follows the inputs and can be
read from the local HMI or via SPA communication.
When an input is set, the respective output is set for a user defined time. If the input signal
remains set for a longer period, the output will remain set until the input signal resets.
INPUTn
OUTPUTn
IEC09000732 V1 EN-US
Figure 246: BINSTATREP logical diagram
18.7.3
Setting guidelines
The pulse time
output can be set or reset individually, but the pulse time will be the same for all outputs in the
entire BINSTATREP function.
Bay control REC670
Application manual
There is a risk of flash wear out if the disturbance report triggers too often.
IEC 61850
identification
BINSTATREP
t
t is the only setting for the Logical signal status report (BINSTATREP). Each
© Copyright 2017 Hitachi Power Grids. All rights reserved
GUID-E7A2DB38-DD96-4296-B3D5-EB7FBE77CE07 v2
GUID-E0247779-27A2-4E6C-A6DD-D4C31516CA5C v3
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
GUID-F9D225B1-68F7-4D15-AA89-C9211B450D19 v3
t
IEC09000732-1-en.vsd
GUID-BBDA6900-4C1A-4A7C-AEA5-3C49C2749254 v2
Section 18
Monitoring
495