Section 9
Voltage protection
LOVPTUV is used for signallization only through an output contact or through the event
recording function.
9.5.3
Setting guidelines
Loss of voltage check (LOVPTUV) is in principle independent of the protection functions. It
requires to be set to open the circuit breaker in order to allow a simple system restoration
following a main voltage loss of a big part of the network and only when the voltage is lost
with breakers still closed.
All settings are in primary values or per unit. Set operate level per phase to typically 70% of the
global parameter
9.5.3.1
Advanced users settings
For advanced users the following parameters need also to be set. Set the length of the trip
pulse to typical
(LOVPTUV), if some but not all voltage are low, to typical 5.0 seconds and set the time delay
for enabling the function after restoration
226
UBase level. Set the time delay tTrip =5-20 seconds.
tPulse =0.15 sec. Set the blocking time tBlock to block Loss of voltage check
© Copyright 2017 Hitachi Power Grids. All rights reserved
tRestore to 3 - 40 seconds.
1MRK 511 401-UEN Rev. K
SEMOD171929-4 v5