ABB Relion 670 Series Applications Manual page 191

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UEN Rev. K
IEC05000465 V2 EN-US
Figure 90: Typical connection for STBPTOC in 1½-breaker arrangement.
8.10.3
Setting guidelines
The parameters for Stub protection STBPTOC are set via the local HMI or PCM600.
The following settings can be done for the stub protection.
GlobalBaseSel : Selects the global base value group used by the function to define IBase , UBase
SBase . Note that this function will only use IBase value.
and
Operation : Off / On
ReleaseMode : This parameter can be set Release or Continuous . With the Release setting the
function is only active when a binary release signal RELEASE into the function is activated. This
signal is normally taken from an auxiliary contact (normally closed) of the line disconnector
and connected to a binary input RELEASE of the IED. With the setting
is activated independent of presence of any external release signal.
I> : Current level for the Stub protection, set in % of IBase . This parameter should be set so that
all faults on the stub can be detected. The setting should thus be based on fault calculations.
t : Time delay of the operation. Normally the function shall be instantaneous.
8.11
Pole discordance protection CCPDSC
Bay control REC670
Application manual
© Copyright 2017 Hitachi Power Grids. All rights reserved
Section 8
Current protection
M12909-3 v5
Continuous the function