Section 25
Requirements
The standard does not define the sample rate for data, but in the UCA users group
recommendations there are indicated sample rates that are adopted, by consensus, in the
industry.
There are two sample rates defined: 80 samples/cycle (4000 samples/sec. at 50Hz or 4800
samples/sec. at 60 Hz) for a merging unit "type1" and 256 samples/cycle for a merging unit
"type2". The IED can receive data rates of 80 samples/cycle.
Note that the IEC/UCA 61850-9-2LE standard does not specify the quality of the sampled
values, only the transportation. Thus, the accuracy of the current and voltage inputs to the
merging unit and the inaccuracy added by the merging unit must be coordinated with the
requirement for actual type of protection function.
Factors influencing the accuracy of the sampled values from the merging unit are for example
anti aliasing filters, frequency range, step response, truncating, A/D conversion inaccuracy,
time tagging accuracy etc.
In principle the accuracy of the current and voltage transformers, together with the merging
unit, shall have the same quality as direct input of currents and voltages.