ABB Relion 670 Series Applications Manual page 608

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 25
Requirements
In isolated or high impedance earthed systems the phase-to-earth fault is not the
dimensioning case. Therefore, the resistance of the single secondary wire can always be used
in the calculation for this kind of power systems.
25.1.5
General current transformer requirements
The current transformer ratio is mainly selected based on power system data for example,
maximum load and/or maximum fault current. It should be verified that the current to the
protection is higher than the minimum operating value for all faults that are to be detected
with the selected CT ratio. It should also be verified that the maximum possible fault current is
within the limits of the IED.
The current error of the current transformer can limit the possibility to use a very sensitive
setting of a sensitive residual overcurrent protection. If a very sensitive setting of this function
will be used it is recommended that the current transformer should have an accuracy class
which have an current error at rated primary current that is less than ±1% (for example, 5P). If
current transformers with less accuracy are used it is advisable to check the actual unwanted
residual current during the commissioning.
25.1.6
Rated equivalent secondary e.m.f. requirements
With regard to saturation of the current transformer all current transformers of high
remanence and low remanence type that fulfill the requirements on the rated equivalent
limiting secondary e.m.f. E
CT (TPZ) is not well defined as far as the phase angle error is concerned. If no explicit
recommendation is given for a specific function we therefore recommend contacting ABB to
confirm that the non remanence type can be used.
The CT requirements for the different functions below are specified as a rated equivalent
limiting secondary e.m.f. E
specified according to other classes and standards are given at the end of this section.
25.1.6.1
Breaker failure protection
The CTs must have a rated equivalent limiting secondary e.m.f. E
to the required rated equivalent limiting secondary e.m.f. E
³
E
E
al
EQUATION1380 V2 EN-US
where:
I
op
I
pr
I
sr
I
r
R
ct
R
L
S
R
602
below can be used. The characteristic of the non remanence type
al
according to the IEC 61869-2 standard. Requirements for CTs
al
æ
I
= ×
×
×
sr
5 I
R
ç
alreq
op
ct
I
è
pr
The primary operate value (A)
The rated primary CT current (A)
The rated secondary CT current (A)
The rated current of the protection IED (A)
The secondary resistance of the CT (W)
The resistance of the secondary cable and additional load (W). The loop resistance containing the
phase and neutral wires, must be used for faults in solidly earthed systems. The resistance of a single
secondary wire should be used for faults in high impedance earthed systems.
The burden of an IED current input channel (VA). S
channel for I
=5 A
r
© Copyright 2017 Hitachi Power Grids. All rights reserved
ö
S
+
+
R
R
÷
L
2
I
ø
r
=0.020 VA/channel for I
R
1MRK 511 401-UEN Rev. K
that is larger than or equal
al
below:
alreq
=1 A and S
=0.150 VA/
r
R
Bay control REC670
Application manual
M11615-3 v3
SEMOD53723-1 v1
M11616-3 v2
M11621-3 v5
(Equation 197)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rec670

Table of Contents