ABB Relion 670 Series Applications Manual page 460

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 17
Logic
Phase segregated trip L1, L2 and L3
from example line differential or
distance protection
Phase selection L1, L2 and L3 from
external phase selection logic
Trip by communication scheme of
distance protection if required to
provide a single pole trip
Trip by communication scheme of
earth fault protection if required to
provide single pole trip
TR3P
To activate lockout
To reset lockout
IEC05000545 V6 EN-US
Figure 234: The trip logic function SMPPTRC used for single-phase tripping application
17.1.3.3
Single-, two- or three-phase tripping
The single-/two-/three-phase tripping mode provides single-phase tripping for single-phase
faults, two-phase tripping for two-phase faults and three-phase tripping for three-phase
faults. The operating mode is always used together with an autoreclosing scheme with setting
ARMode = 1/2/3 ph or ARMode = 1/2 ph .
The functionality is very similar to the single-phase scheme described above. However, in
addition to the connections for single phase SMBRREC must also be informed that the trip is
two phases by connecting the output TR2P to the input TR2P in the SMBRREC function.
17.1.3.4
Lock-out
The SMPPTRC function block is provided with possibilities to initiate lockout. The lockout can
be set to only activate the circuit breaker lockout output CLLKOUT or to both initiate the
circuit breaker lockout output and to maintain the trip signal outputs TRIP, TRL1, TRL2, TRL3,
and TR3P (latched).
If external conditions are required to initiate a circuit breaker lockout, it can be achieved by
activating input SETLKOUT. The setting
trip will not activate lockout so only initiation of the input SETLKOUT will result in lockout. This
is normally the case for overhead line protection where most faults are transient. Unsuccessful
autoreclosing and back-up zone tripping can in such cases be connected to initiate lockout by
activating the input SETLKOUT.
454
Protection functions with 3
phase trip, for example time
delayed overcurrent protection
SMBRREC
PREP3P
To prepare 3 phase trip
for any trip signal
© Copyright 2017 Hitachi Power Grids. All rights reserved
SMPPTRC
TMGAPC
BLOCK
BLKLKOUT
TRINALL
TRINL1
TRINL2
TRINL3
TRINN
PSL1
PSL2
PSL3
1PTRZ
1PTREF
P3PTR
SETLKOUT
RSTLKOUT
STDIR
AutoLock = Off means that the internal three-phase
1MRK 511 401-UEN Rev. K
TRIP
TRL1
TRL2
TRL3
TRN
TR1P
TR2P
TR3P
CLLKOUT
START
STL1
STL2
STL3
STN
FW
REV
IEC05000545-6-en.vsdx
Bay control REC670
Application manual
M14828-15 v5
M14828-18 v7