ABB Relion 670 Series Applications Manual page 486

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 18
Monitoring
100 MVA
242/15,65 kV
100MVA
15,65kV
IEC09000041-1-EN V1 EN-US
Figure 243: Single line diagram for generator application
In order to measure the active and reactive power as indicated in figure 243, it is necessary to
do the following:
1.
Set correctly all CT and VT data and phase angle reference channel
Section
2.
Connect, in PCM600, measurement function to the generator CT & VT inputs
3.
Set the setting parameters for relevant Measurement function as shown in the following
table:
480
220kV Busbar
300/1
Yd5
15 / 0,1kV
P
G
4000/5
"Setting of the phase reference
© Copyright 2017 Hitachi Power Grids. All rights reserved
IED
U
, U
L1L2
L2L3
Q
IEC09000041-1-en.vsd
channel") using PCM600 for analog input channels
1MRK 511 401-UEN Rev. K
PhaseAngleRef (see