Section 15
Control
QB7OPTR (bay 1)
. . .
. . .
. . .
QB7OPTR (bay n)
VPQB7TR (bay 1)
. . .
. . .
. . .
VPQB7TR (bay n)
EXDU_BB (bay 1)
. . .
. . .
. . .
EXDU_BB (bay n)
IEC04000510 V1 EN-US
Figure 198: Signals from bypass busbar to busbar earthing switch
15.4.7.3
Signals in double-breaker arrangement
The busbar earthing switch is only allowed to operate if all disconnectors of the bus section
are open.
(WA1)A1
(WA2)B1
IEC04000511 V1 EN-US
Figure 199: Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
BB_DC_OP
VP_BB_DC
EXDU_BB
These signals from each double-breaker bay (DB_BUS) are needed:
Signal
QB1OPTR
QB2OPTR
VPQB1TR
VPQB2TR
EXDU_DB
These signals from each bus-section disconnector bay (A1A2_DC) are also needed. For
B1B2_DC, corresponding signals from busbar B are used. The same type of module (A1A2_DC)
is used for different busbars, that is, for both bus-section disconnectors A1A2_DC and
B1B2_DC.
388
Section 1
A1A2_DC(BS)
B1B2_DC(BS)
BB_ES
DB_BUS
All disconnectors of this part of the busbar are open.
The switch status of all disconnectors on this part of the busbar are valid.
No transmission error from any bay that contains the above information.
QB1 is open.
QB2 is open.
The switch status of QB1 is valid.
The switch status of QB2 is valid.
No transmission error from the bay that contains the above information.
© Copyright 2017 Hitachi Power Grids. All rights reserved
BB_DC_OP
&
VP_BB_DC
&
EXDU_BB
&
en04000510.vsd
Section 2
A2
B2
BB_ES
DB_BUS
en04000511.vsd
1MRK 511 401-UEN Rev. K
M15053-83 v4
Bay control REC670
Application manual