ABB Relion 670 Series Applications Manual page 547

Bay control
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 401-UEN Rev. K
IEC17000044 V1 EN-US
Figure 260: Merging unit
20.3.2
Setting guidelines
For information on the merging unit setting guidelines, see section
communication
20.4
Routes
20.4.1
Application
Setting up a route enables communication to a device that is located in another subnetwork.
Routing is used when the destination device is not in the same subnetwork as the default
gateway.
The route specifies that when a package is sent to the destination device it should be sent
through the selected router. If no route is specified the source device will not find the
destination device.
20.4.2
Setting guidelines
Routes are configured using the Ethernet configuration tool in PCM600.
Operation for the route can be set to On / Off by checking and unchecking the check-box in the
operation column.
Gateway specifies the address of the gateway.
Destination specifies the destination.
Destination subnet mask specifies the subnetwork mask of the destination.
Bay control REC670
Application manual
IEC17000044-1-en.vsdx
protocol.
© Copyright 2017 Hitachi Power Grids. All rights reserved
Section 20
Ethernet-based communication
GUID-3449AB24-8C9D-4D9A-BD46-5DDF59A0F8E3 v1
IEC/UCA 61850-9-2LE
GUID-19616AC4-0FFD-4FF4-9198-5E33938E5ABD v1
GUID-2C4A312A-00DC-44C8-B2D9-CD0822E1C806 v1
541