Transmission delay time
The transmission delay time includes the input transmission delay time and the output transmission delay time.
Input transmission delay time
The input transmission delay time shows the following.
• The time from signal (RX) input into the slave station until the master station device turns ON or OFF.
• The time from data (RWr) input into the slave station until the time data is stored in the master station device.
■Calculation method for input transmission delay time
• Input transmission delay time (max.)=Ls×2+SS[ms]
Item
Ls
SS
Output transmission delay time
The output transmission delay time shows the following.
• The time from master station device turning ON or OFF until the slave station output (RY) turns ON or OFF.
• The time from setting data in the master station device until the data is output to the slave station (RWw).
■Calculation method for output transmission delay time
• Output transmission delay time (max.)=Ls+SS[ms]
Item
Ls
SS
7 CC-Link IE Field Network Basic FUNCTION
94
7.4 Processing Time
Description
Link scan time [ms]
Slave station input reflection processing time [ms] (manual for slave station in use)
Description
Link scan time [ms]
Slave station output reflection processing time [ms] (manual for slave station in use)