Download Print this page

Mitsubishi Electric MELIPC MI5000 Series User Manual page 87

Hide thumbs Also See for MELIPC MI5000 Series:

Advertisement

Access to guaranteed linked devices
Before and after normal access to linked devices, read/write data is assured manipulating the start and end of assurance of
read/write data.
(1)
RX, RWr
Ò
Ó
Ô
(1) Master station
(2) Slave station
(3) Cyclic transmission
No.
Operation
Start the assurance of read/write data.
• CCPU_StartCCIEFBDataAssurance
Read/write the link device.
Assurance of read/write data is ended.
• CCPU_EndCCIEFBDataAssurance
■Function list
Function name
CCPU_StartCCIEFBDataAssurance
CCPU_EndCCIEFBDataAssurance
For details on the C Controller module dedicated functions, refer to the following manual.
MELIPC MI5000 Series Programming Manual (VxWorks)
Precautions
After starting data assurance of link devices, always end it. Otherwise, the updating of the input status for own station link
devices and the output status of link devices from own station to other stations does not restart.
RY, RWw
(3)
Status
Update stops of the link device input status for own station (RX, RWr) and the output status (RY,
RWw) from own station to other stations.
■Read data
Update is stopped of the link device input status for own station (RX, RWr), so the read data is
assured.
■Write data
Update of the link device input status from own station (RY, RWw) to other stations is stopped, so the
read data is not sent to slave stations.
Restart refresh of link device input status for own station (RX, RWr) and for output status (RY, RWw)
for own station to other stations. (The own station output status written in Step  undergoes data
assurance and is sent to other stations. )
Description
Starts data assurance for access to a link device of CC-Link IE Field Network Basic.
Ends data assurance for access to a link device of CC-Link IE Field Network Basic.
(2)
RX, RWr RY, RWw
7 CC-Link IE Field Network Basic FUNCTION
85
7.1 Cyclic Transmission
7

Advertisement

loading

This manual is also suitable for:

Melipc mi5122-vw