Mitsubishi Electric MELIPC MI5000 Series User Manual page 60

Hide thumbs Also See for MELIPC MI5000 Series:

Advertisement

Item
Network Status
Selected Station Communication Status Monitor
Operation Test
Information
Confirmation/Setting
6 CC-Link IE Field Network FUNCTION
58
6.4 CC-Link IE Field Network diagnosis
Total Slave Stations (Parameter)
Total Slave Stations (Connected)
Current Link Scan Time
Number of Station Errors Detected
Constant Link Scan Settings Value
Network configuration diagram
Disconnected station monitoring status
[Communication Test] button
[Cable Test] button
[Link Start/Stop] button
[Reserved Station Function Enable]
button
[Enable/Disable Ignore Station Errors]
button
Description
Displays the total number of slave stations (No. of slave stations) set in "Network
Configuration Settings" under "Basic Settings".
Displays the total number of slave stations (No. of slave stations) actually carrying out
baton pass in the CC-Link IE Field Network.
The displayed network link scan time is displayed.
Displays the number of stations with error occurrences on the displayed network.
Displays values set in "Application Settings" "Supplementary Cyclic Settings" "Constant
Link Scan Time".
Displays CC-Link IE Field Network topology and each station status.
If the status of each station is not displayed, confirm that there is no master station or
station number duplication. ( Page 60 Network configuration diagram)
Displays disconnected stations in station settings in "Basic Settings" "Network
Configuration Settings", but have never been data linked.
However, even if they have been data linked once, disconnected stations such as those
below will be displayed.
• Stations that have had network reconnection processing as a result of the cable being
removed and then reinserted or OFF to ON, or that are disconnected after reconnection
has completed
• Disconnected stations that have been removed from the network configuration by
clicking the [Update] button
"Other Modules" icons are stations that have not carried out data link.
Other than "Other Modules" icons are stations that have been disconnected after carrying
out data link.
Click the [Legend] button to confirm details of displayed icons.
Displays status of the station selected in "Network status". ( Page 62 Selected station
communication status monitor)
Test communication. ( Page 63 Communications test)
Test the cable. ( Page 64 Cable test)
Start/stop a link. ( Page 65 Link start/stop)
Temporarily clear reserved stations and return temporarily cleared stations to reserved
stations. ( Page 67 Reserved station temporary clear/remove)
Temporarily set slave stations to error disabled stations. ( Page 69 Temporary error
disabled station settings/remove)