If the WIN RDY LED is not lit
Check item
Is the WIN RDY LED off?
Is the WIN RDY LED flashing?
If the MAIN ERR LED is not off
Check item
Is the MAIN ERR LED not flashing?
Is the MAIN ERR LED not on?
If the MAIN RUN LED is blinking slowly
Check item
Is the execution of the script file (STARTUP.CMD) completed?
If the FAN LED is not OFF
Check item
Is the FAN LED on?
Is the FAN LED not flashing?
If the BATTERY LED is not off
Check item
Is the BATTERY LED on?
Corrective action
If Windows was shut down from the Start menu of Windows, use the MELIPC
RESET/WIN RESET switch to force a reset of the Windows part.
The Windows part cannot start, so recover Windows.
If Windows recovery fails, this may indicate a hardware fault of this product.
Consult your local Mitsubishi representative.
• The Windows part is preparing or shutting down.
• If shutdown processing has been carried out, then wait, and if the status
does not change, connect a display to the DisplayPort in order to confirm
that there is nothing preventing a shutdown, such as a program still
operating, or a file requiring a save.
• If there is no reason for shutdown not to complete, either run the MELIPC
shutdown function again or shut down Windows from the Windows Start
menu.
• If the power was turned on or the Windows part was restarted, wait until the
Windows part starts. If it does not start for a long time, connect a display to
the DisplayPort. If an error, such as repeated restarts, occurs repeatedly,
restart the Windows part in Safe mode.
• If the Windows part does not start for a long period of time after restarting
the Windows part, reset this product by a switch operation or turn the power
of the product OFF and ON.
• If this symptom occurs repeatedly, data on the CFast card may be
corrupted. In that case, recover Windows on this product.
Corrective action
Check the error code in MI Configurator and handle in accordance with the
error code. ( Page 220 List of Error Codes)
Corrective action
Perform the script initialization function so that the script file (STARTUP.CMD)
does not run. After performing the function, check the contents of the renamed
script file (STARTUP.BAK), and remove the factor that prevents completion of
the script file. (MELIPC MI5000 Series User's Manual (Startup))
Corrective action
Clean the fan module, and then execute an Alert reset from the online menu.
Exchange the fan module, and then execute an Alert reset from the online
menu.
Corrective action
Replace the battery.
Appendix 1 Troubleshooting by Symptom