Error code
41E0H
41E7H
41E8H
41E9H
41EBH
41ECH
41EDH
41F3H
4A02H
4A03H
4B00H
4B02H
4B03H
4B04H
APPX
234
Appendix 2 List of Error Codes
Error name
File related error
File related error
File related error
File related error
File related error
File related error
File related error
File related error
Link-related error
Link-related error
Target related
Target related
Target related
Target related
Description
There is an error with the specified drive
(memory), or this does not exist.
The format information data of the specified
drive (memory) is abnormal.
The format information data of the specified
drive (memory) is abnormal.
The specified file is being accessed.
There is an error in the specification method
of the file name.
The file system of the specified drive
(memory) is logically corrupted.
The specified drive (memory) does not have
enough continuous free space. (There is
free space for the file, but the continuous
free space is insufficient.)
The size of the specified file exceeds 4 GB
minus 2 bytes.
The specified station cannot be accessed.
A request for network test was issued.
An error occurred on the access destination
or the relay station. Alternatively, the
specified connection destination (request
destination module I/O number) is not
supported.
There is no request addressed to the
MELIPC.
• The specified route is not supported by
the version of the specified MELIPC.
• The CPU of the communication target is
not mounted.
• A device that does not support
communications is on the specified route.
The specified connection destination
(request destination module I/O number) is
not supported.
Corrective action
Back up the data of the /ROM folder, and
then initialize the memory.
Back up the data of the /ROM folder, and
then initialize the memory.
Back up the data of the /ROM folder, and
then initialize the memory.
Execute it again after a while.
Check the file name, and execute the
request again.
Back up the data of the /ROM folder, and
then initialize the memory.
Delete unnecessary files, and then execute
again.
Reduce the size of the specified file through
creation or a size change. Alternatively,
separate the file into multiple files to reduce
the file size.
Check that the operating mode is not set to
offline.
Check that there are no mistakes in the
network No. or station No. settings.
Check request data such as SLMP.
• Check the error occurred on the specified
access destination or relay station to the
station to be accessed, and take the
corrective actions.
• Check the request data connection
destination settings (request destination
module I/O number).
• Check the stop error, and take the
corrective actions.
Perform the operation to the module that
can perform the specified function.
• Check the specified route.
• Check the mounting status of the CPU
module.
• Check the stop error, and take the
corrective actions.
In other device settings, an illegal value is
set for the target module header I/O
number. Change to a header I/O number for
an existing unit, and carry out
communications again.