Download Print this page

Mitsubishi Electric MELIPC MI5000 Series User Manual page 231

Hide thumbs Also See for MELIPC MI5000 Series:

Advertisement

Codes of errors detected other than by the self-diagnosis function (4000H to 4FFFH)
The following table shows the codes of errors not detected by a means other than the self-diagnosis function of this product.
Error code
Error name
4001H
Common error
4002H
Common error
4003H
Common error
4004H
Common error
4005H
Common error
4006H
Common error
4008H
Common error
4021H
File related error
4022H
File related error
4023H
File related error
4024H
File related error
4025H
File related error
4027H
File related error
4028H
File related error
4029H
File related error
402AH
File related error
402BH
File related error
402CH
File related error
4030H
Device specification error
4031H
Device specification error
4032H
Device specification error
Description
An unsupported request was executed.
An unsupported request was executed.
Command for which a global request cannot
be performed was executed.
A request was issued to the system file.
The volume of data to be handled by the
specified request is too large.
Initial communication has failed.
The MELIPC is busy. (The buffer is not
empty.)
The specified drive (memory) does not exist
or there is an error.
The file with the specified file name or file
number does not exist.
The file name and file number of the
specified file do not match.
The specified file cannot be handled.
The specified file is currently processing a
request from another engineering tool.
The specified range is larger than the file
size.
The same file already exists.
The specified file capacity cannot be
reserved.
The specified file has an error.
The request cannot be executed in the
specified drive (memory).
At present, request details cannot be run.
The specified device name cannot be
handled.
• The specified device number is out of
range.
• MELIPC does not support the specified
device name.
A device name that has an error in the
device qualification, or that can be used in
SLMP random readout/random write (word
unit)/monitor registration/monitor command
(TS, TC, SS, SC, CS, CC) is specified.
Corrective action
• Check command data such as SLMP.
• Check the model selected by the
engineering tool.
• Check command data such as SLMP.
• Check the model selected by the
engineering tool.
• Run again. If the same error is displayed
again, this may indicate a hardware fault.
Consult your local Mitsubishi
representative.
Check command data such as SLMP.
Check command data such as SLMP.
Check command data such as SLMP.
When using Ethernet communication, shift
the communication start timing.
Execute it again after a while.
• Check the specified drive (memory)
status.
• Back up the data of the /ROM folder, and
then initialize the memory.
Check the specified file name and file
number.
Delete the file, and then create a file again.
The specified file cannot be handled.
Forcibly execute the request. Or, execute it
again once the processing from another
engineering tool has been completed.
Check the specified range, and access
within the range.
Forcibly execute the request. Or, change
the file name and execute the request
again.
• Review the specified file capacity, and
execute the request again.
• Delete unnecessary files of the /ROM
folder, and then execute again.
Back up the data of the /ROM folder, and
then initialize the memory. Next, try writing
the file again.
• STOP MELIPC, and execute again.
• Delete unnecessary files of the /ROM
folder, and then execute again.
Execute it again after a while.
Check the specified device name.
• Check the specified device number.
• Check the specified device name.
• Check the specified device modification
method.
• Check the specified device name.
APPX
Appendix 2 List of Error Codes
A
229

Advertisement

loading

This manual is also suitable for:

Melipc mi5122-vw